Ac Reactor Electrical Performance And Standards
Ac Reactor Electrical Performance And Standards
1. Rated working voltage: AC110V~1140V (conventional voltage 3∮380V, special needs to be customized)
2. Rated working frequency: 50HZ/60HZ
3. Rated voltage drop: 1%-14% (conventional reactance rate input 2% output 4%, 1% current limiting, 6%7% suppress 5th, 7th and 11th harmonics, 12%14% suppress 3rd and above harmonics)
4. Working withstand voltage: core to winding 3000VAC/50HZ/5MA/60S without arcing and breakdown (factory test environment humidity <55%)
5. Insulation resistance: core to winding 1000VDC≥100M;
6. Working temperature rise: core <80K (temperature calculation, core temperature minus ambient temperature) coil winding temperature <95K (DC resistance test method)
7. Working noise: ≤60dB (tested at a horizontal distance of 1M from the reactor);
8. Product implementation standards: GB19212.1-2008 GB1094.6-2011