Overview
The Static Transfer Switch (STS) is a device that automatically transfers power supply from one source to another in the event of a power failure, voltage sag, or other electrical anomalies. It operates by monitoring the power supply from two independent power sources, typically the main power supply and a backup generator or uninterruptible power supply (UPS). When the STS detects a fault or failure in the main power supply, it will automatically switch the power source to the backup supply, ensuring continuity of power supply to critical equipment.
Single phase wall-mounted25-125A | 3 Phases 63A-400A | Single-phase 3URackmount63-125A |
Features
● Intelligent monitor, diagnostics and alarming
● Priority source: the user chooses one source as main source and another as standby
● Transfer time : 5ms maximum auto transfers between AC power sources
● Protection: if the STS fail, the system will choose one input source as fix source, to ensure uninterruptible power supply
● Break-before-made switching, automatic switching
Time of transfer
Application
- STS are commonly used in data centers, hospitals, manufacturing facilities, and other critical infrastructure where continuous power supply is essential. They are particularly useful in situations where the failure of power supply can result in costly downtime or loss of data.
- Automatic control system of data rooms, communication rooms and power industry, power supply system of petrochemical industry, security prevention system of intelligent building and other mission critical environments.
- In summary, Static Transfer Switches are essential components in applications where continuity of power supply is critical. They are used in a wide range of industries including data centers, hospitals, manufacturing facilities, telecommunications, and transportation infrastructure.
IDC | Power Plant | Financial industry | Airport |
Specifications
Capacity | 25A~125A | 63A~400A | |||||||||||
AC INPUT | |||||||||||||
Phases | single Phase | 3Phase | |||||||||||
Voltage | AC 220V±15% | AC 380V±15% | |||||||||||
Frequency | 50/60Hz | ||||||||||||
AC OUTPUT | |||||||||||||
Phases | single Phase | 3 Phase | |||||||||||
Voltage | AC 220V±15% | AC 380V±15% | |||||||||||
Frequency | 50/60Hz | ||||||||||||
Max Current(/Phase) | 25A | 32A | 40A | 63A | 100A | 125A | |||||||
Connectors | Terminal block | ||||||||||||
Breaker | MCB*5(With Bypass) | MCCB(Molded case circuit breaker) | |||||||||||
PERFORNMANCE | |||||||||||||
Transfer Time | ≤6ms(typical) | ||||||||||||
Transfer Number | 1P (Optional:1P + N L-poles.,N-poles) | 3P (Optional:3P + N) | |||||||||||
Priority | Input Source-A is Priority | ||||||||||||
Transfer Type | SCR / First Disconnect Then Connect | ||||||||||||
Efficiency | ≥98% | ||||||||||||
DISPLAY | |||||||||||||
LED | Working Status | ||||||||||||
LCD(Optional) | Voltage \ Current\Power | ||||||||||||
OTHER | |||||||||||||
Standards | GB/T 34940-2017/IEC 62310:2006 | ||||||||||||
Co0ling | Air cooling; Ac fan start when over temperature | ||||||||||||
Insulation resistance | DC 500V ≥20MΩ | ||||||||||||
Insulation withstand voltage | AC1800V 10mA/1 Minute | ||||||||||||
Operating Temperature | 0℃~45℃ | ||||||||||||
Relative humidity | 0~99%(Non-condensed state) | ||||||||||||
Operating Altitude | ≤1500m | ||||||||||||
Main parameters of STS for single-phase 25A-125A | |||||||||||||
MODEL | STS-1125W | STS-1132W | STS-1140W | STS-1163W | STS-11100W | STS-11125W | |||||||
Max Current(/Phase) | 25A | 32A | 40A | 63A | 100A | 125A | |||||||
Dimensions(W*D*H) | 430*350*88mm | ||||||||||||
Net Weight | 16kg | 17kg | 18kg | 19kg | 20kg | 22kg | |||||||
Main parameters of STS for single-phase 3U rack mount 63A-125A | |||||||||||||
MODEL | STS-1163 | STS-11100 | STS-11125 | ||||||||||
Max Current(/Phase) | 63A | 100A | 125A | ||||||||||
Dimensions(W*D*H) | 430*350*88mm | ||||||||||||
Net Weight | 13kg | 15kg | 16kg | ||||||||||
Main parameters of STS for three phases 63A-400A | |||||||||||||
MODEL | STS-3363 | STS-33100 | STS-3160 | STS-33250 | STS-33300 | STS-33400 | |||||||
Max Current(/Phase) | 63A | 100A | 160A | 250A | 300A | 400A | |||||||
Dimensions(W*D*H) | 600*600*1000mm | 600*800*1760mm | |||||||||||
Net Weight | 65kg | 70kg | 80kg | 105kg | 155kg | 215kg |
- All specifications are subject to change without prior notice.
- Custom-made specifications are acceptable.