800 kVA 3 Phase Uninterruptible Power Supply UPS
- Phase:
- Single/Three phase
- Input voltage:
- 220/380V, 230/400V ±20% or customized
- Output voltage:
- 220/380V, 230/400V ±1-5%
- Frequency:
- 50/60Hz
- Power factor:
- 0.8-1
- Type of technology:
- Servo type with roller carbon brush
- Type of regulation:
- Independent voltage control
- Display:
- LED/Touch Screen HMI
- Installation:
- Indoor/Outdoor
800 kVA 3 Phase Uninterruptible Power Supply UPS
Quick Detail:
Online Type UPS-5KVA to 200KVA
Dimension(W×D×H)mm: 1000×800×2260(1or2 cabinet)
Weight: 950kg
Description:
In the event of an AC power failure, the UPS will automatically transfer to battery power and continue to provide power without any interruption for the full amount of time you select. When power returns, the UPS will automatically recharge the batteries for the next unexpected power outage or disturbance.
MODERN BUD Series Industrial UPS are for the bad grid environment and the impact of power system load on the power requirements of high reliability, using the most advanced multi-CPU control technology developed by frequency pure-line intelligent UPS. MODERN UPS advantage lies in ultra-high-power design; single maximum power 750kVA, and in parallel multi-machine power up to 3000kVA, providing critical power protection for a range of applications.
Applications:
- Computer and data centers
- Broadcasting and telecommunication
- Industrial process manufacturing
- Medical equipment and healthcare facilities
- Education and research
- Transport systems
- Emergency lighting systems
- Financial systems and services
- Any areas needing critical power management
Specifications:
Model | BUD220 -3050 | BUD220 -3100 | BUD220 -3150 | BUD220 -3300 | BUD220 -3500 | BUD220 -31000 | BUD220 -32000 | ||
DC Input | Rated Input Voltage (V) | 220 | |||||||
Rated Input Current (A) | 25.3 | 49.4 | 74 | 148 | 247 | 494 | 988 | ||
Input DC Voltage Range (V) | 180 ~ 300 | ||||||||
AC Input | Rating Input Voltage (V) | 220 ( Single-phase ) | 380 (3 phase 4 wires) | ||||||
Voltage Range (V) | 220 ± 15% | 380 ± 15% | |||||||
Input Frequency (Hz) | 45 ~ 60 | ||||||||
Power Factor (PF) | 0.9 | ||||||||
Bypass Input | Input Voltage Range (V) | 380 ± 15% (3 phase 4 wires) | |||||||
Rated Input Current (A) | 7.6 | 15.2 | 22.8 | 45.6 | 76 | 152 | 304 | ||
AC Output | Rated Capacity (KVA) | 5 | 10 | 15 | 30 | 50 | 100 | 200 | |
Rated Output Power (KW) | 4 | 8 | 12 | 24 | 40 | 80 | 160 | ||
Rated Output Voltage | 380VAC , 50Hz (3 phase 4 wires) | ||||||||
Rated Output Current (A) | 7.6 | 15.2 | 22.8 | 45.6 | 76 | 152 | 304 | ||
Output Voltage Accuracy (V) | 380 ± 3% | ||||||||
Output Frequency Accuracy (Hz) | 50 ± 0.05 | ||||||||
Waveform Deviation Factor (THD) - Liner Load |
≤ 5% | ||||||||
Three-Phase load Unbalance Ability | ≤ 100% | ||||||||
Dynamic Response ( load 0 ←→ 100%) |
5% | ||||||||
Power Factor (PF) | 0.8 | ||||||||
Load ability | 150%,10 seconds | ||||||||
Crest Factor (CF) | 3:1 | ||||||||
Inverted Efficiency (80% resistance load ) |
92% | ||||||||
Switch Time (ms) |
AC ⇋ DC | 0 | |||||||
|
4 | ||||||||
Working Environment | Insulation Strength | 2000V AC ,1 minute | |||||||
Noise (1 meter) | ≤ 50dB | ||||||||
Using Condition Temperature | -10 ℃ ~+ 50 ℃ | ||||||||
Humidity | 0~90%, no condensing | ||||||||
Using Altitude (m) | ≤ 2000 | ||||||||
Machine Dimension | Width×Depth×Height(mm) | 550×485×1200 | 800×600×2260 (1 or 2 cabinet) |
1000×800 × 2260 (1 or 2 cabinet) |
|||||
Reference Weight (Kg) | 90 | 200 | 250 | 450 | 620 | 950 | 2300 | ||
Fault dry contact | Inverter abnormal,AC abnormal,battry abnormal, load abnormal,UPS abnormal | ||||||||
Protection function | Input reversing protection,input low-voltage protection, output over-load protection,output short-circuit protection, over-heat protection |
Competitive Advantage:
- Adopt power standard screen tank design
- High output power factor diminishes need for UPS over sizing
- Constant high efficiency at full and partial load
- Extremely low output distortion
- Best in class for variable load applications
- Galvanic isolation which provide additional critical power protection
- Municipal electric power supply with DC inverter power 0 conversion delay
- Adopt DSP digital control technology intelligent detection and monitoring function
- High-speed IGBT drive inverter
- No fountain contact and RS232/485 monitoring